DIMENSIONS:
INSTALLATION:
The controller can be installed inany positionon a
flat surfaceusing electrical box [Type-3Module].
Tomeasure room temperature by internal sensor
and choosingwall mountingmethod, it is
recommended to be installed 1.5m (about 5 ft.)
above the floor in the area at average temperature
conditions.
For all kinds of mountingmethod, theproductmust
be installed inan areawith good air circulation.
Do not install the controller where it may be
affected by:
Draughts or dead air spots behind doors
and in corners.
Hot or coldair fromducts.
Radiant heat fromsun or appliances.
Concealed pipes and chimneys
WIRINGTERMINAL:
1 2 3 4 5 6 7 8
1&2 –RelayOutput
3 – 0Vac
4 – 24Vac
5 –Digital Input
6 – 2…10VdcOR 4…20mAanalog output
7&8 –PT1000RemoteSensor