CLASSIFICATION
FLOWCONTROLRANGE
LPM (GPM)
PipeDiameter
Minimum
Maximum
(inch)
On-Flow
Off-Flow
On-Flow
Off-Flow
1
15 (4.0)
8 (2.0)
45 (12.0)
41 (11.0)
1-1/4
26 (6.9)
13 (3.4)
75 (20.0)
68 (18.0)
1-1/2
29 (7.0)
20 (5.3)
105 (28.0)
94 (25.0)
2
34 (9.0)
17 (4.5)
120 (32.0)
105 (28.0)
2-1/2
60 (16.0)
34 (9.0)
210 (55.0)
188 (50.0)
3
68 (18.0)
30 (8.0)
288 (76.0)
275 (73.0)
4
128 (34.0)
64 (17.0)
412 (109.0)
360 (95.0)
5
225 (59.0)
113 (30.0)
750 (198.0)
652 (172.0)
6
345 (91.0)
172 (45.0)
1125 (297.0)
975 (258.0)
Paddle
2
3
1
FLOWCONTROLRANGETABLE
This table illustrates the flow control rangeobtained fromexperimental data.
A variationof up to10% canbeexpected, dependingonoperating conditions.
Final adjustmentsshouldbemadeon siteusinga flowmeter.
TYPICAL INSTALLATION
WFS-6000 WATERFLOWSWITCH
Environmental &CombustionControls
Honeywell Automation IndiaLimited
56&57, Hadapsar Industrial Estate,
Pune–411 013, India.
Phone: (91) 2066039400
Fax: (91) 20 6603 9979
APHIWFS001-06-10
Subject to
change
without notice.
Printed in India.
Type
Voltage
Resistence
Load
Lamp
Load
Motor
Load
AC
(Standard)
AC 125V
AC 250V
5A
2.5A
44A
22A
5A
2.5A
DC
DC115V
DC230V
0.3A
0.15A
ELECTRICALRATINGS
1” NPT