VBA216–PRODUCTDATA
Printed inChina.
Subject to changewithout notice.
APEN0H-034CH33A0908_VBA216
DIMENSIONS
Fig. 1
DN
OS#
mm
In
L
T
K
A
B
H
VBA216-020P
20
¾
60
34
38
49.5
30.5
60.5
VBA216-025P
25
1
65
38.5
44
56
34
67
VBA216-032P
32
1¼
75
45
54
65
38
76
VBA216-040P
40
1½
85
51.5
60
78
48
89
VBA216-050P
50
2
95
56.5
73
90
53.5
101
VBA216-065P
65
2½
115
63.5
92
110
64
122
VBA216-080P
80
3
130
83
109
127.5
73
140
Installation
•
Vertical installation of horizontal piping or horizontal installation of vertical piping.
•
Whenmounting the actuator in the fields, before installing theactuator, use anadjustablewrench to
manually rotate the valve stem several times. This rotation breaks the torque thatmay havebuilt up
during long-term storage.
•
Pay attention tomedium flowdirection, make sure the valve tomove in the proper direction, wire
the input lines to the electric actuator correctly.