7
Table4. Signalsat terminals
terminal
mode
modulating
floating
2-position
1
24V~/+ (power)
unused
or
(with feedback)
24V~/+ (power)
unused
or
(with feedback)
24V~/+ (power)
2
common~/-
common~/-
common~/-
3
0[2]...10V (control)
24V~/+ (control signal)
24V~/+ (control signal)
4
24V~/+ (override)
24V~/+ (control signal)
24V~/+ (control signal)
5
0[2]...10V (feedback)
unused
or
(with feedback)
0...10V
unused
or
(with feedback)
0...10V
NOTE: All cables connected to these terminalsmust be equippedwith spark suppression.
Table 5. Internal end switches
terminal
typeof switch
S1
common lead for switchesA andB
S2, S3
change-over switchA (S1/S2 opens andS1/S3 closeswhen shaft adaptermovesCW past 5°; reverts to
original statewhen shaft adaptermovesCCW past 5°).
S5, S6
change-over switchB (S1/S5 opens andS1/S6 closeswhen shaft adaptermovesCW past 85°; reverts to
original statewhen shaft adaptermovesCCW past 85°).