Page 13of 16 APHITEMPCON001-11-04
9.
ReverseAction Setting :
-
Press “SELECT” to choose
“Reverse Setting”, the displaywill show as in fig. 9
-
Press keyone time to switches fromOFF toON.
OFF
: Output1 in normalmode, i.e. 2 - 10Vdc or 4 - 20mA
ON : Output in reversingmode, i.e. 10 - 2Vdc or 20 - 4mA.
-
Press keyone time to switches fromON toOFF.
-
Press “ENTER” key to save the settingvalue.
P V
:
3 0 .
2 °
C
R E V E R S E
O F F
Fig. 9
10.
Display Setting :
-
Press “SELECT” to choose “DisplaySetting”, the displaywill show as in fig.10
-
Press keyone time to switches fromOFF toON.
OFF
:Normalmode, as shown in fig. 2.
ON : Percentagemode, output1 is percent value (2Vdc or 4mA – 0% & 10Vdc
or 20mA–100%) as shown fig.11.
-
Press keyone time to switches fromON toOFF.
-
Press “ENTER” key to save the settingvalue.
P V
:
3 0 .
2 °
C
D I
S P L A Y
O F F
Fig. 10
P V
:
3 0 .
2 °
C
A 0
:
9 1 %
Fig. 11