Page 11of 16 APHITEMPCON001-11-04
4.
Differential setting:
-
Press “SELECT” to choose “Differential Setting”, the displaywill show as in fig.4
-
Press keyone time to stepup the differential settingby0.5°C, itwill stop
incrementing at 3.0°C. The range is 0.5 to 3.0 °C.
-
Press keyone time to stepdown the differential settingby0.5°C. Itwill stop
decrementing at 0.5°C. The range is 3.0 to0.5 °C.
-
Press “ENTER” key to save the settingvalue.
P V
:
3 0 .
2 °
C
D I
F F
1 .
0 °
C
Fig. 4
5.
Proportional BandSetting:
-
Press “SELECT” to choose “ProportionBand
Setting”, thedisplaywill show as in fig.5
-
Press keyone time to stepup theProportional bandby0.1°C. If pressed
continuously formore than ten steps then the valuewill increment by the step of 1.0°C
up to 19.0°C. Release
key to stop the increment of the value.
-
Press keyone time to stepdownProportional Bandby0.1°C If pressed
continuously formore than ten steps then the valuewill decrement by the step of 1.0°C
up to2.0°C. Release key to stop the decrement of the value.
-
Press “ENTER” key to save the settingvalue.
P V
:
3 0 .
2 °
C
P -
B A N D
1 0 .
0 °
C
Fig. 5
6.
Offset Setting:
-
Press “SELECT” to choose “Offset Setting”, the displaywill show as in fig.6
-
Press keyone time to stepupOffset by0.1°C. If pressed continuously for
more than ten steps then the valuewill increment by the step of 1.0°C up to 3.0°C.
Release key to stop increment of the value. The range is –3.0 to3.0 °C.
-
Press keyone time to stepdownOffset by0.1°C. If
pressed continuously formore than ten steps then
the valuewill decrement by the stepof 1.0°Cup to -3.0°C. Release
key to stop increment of the value.
The range is 3.0 to –3.0 °C.
-
Press “ENTER” key to save the settingvalue.
P V
:
3 0 .
2 °
C
O F F S E T
-
1 .
0 °
C
Fig. 6