Page 15of 16 APHITEMPCON001-11-04
13.
F2Setting :
-
Press “SELECT” to choose “F2 setting”, the displaywill show as in fig.15
-
Press keyone time to stepup theAlarmSet point by0.1°C. If is pressed
continuously formore than ten steps then the valuewill increment by the step of 1.0°C
up to60.0°C (for internal sensor) or 110.0°C (for external sensor). Release key to
stop the increment of value.
-
Press keyone time to stepdown theAlarm set point by0.1°C. If pressed
continuously formore than ten steps then the valuewill decrement by the step of 1.0°C
up to 10.0°C (for internal sensor) or -20.0°C (for external sensor).
Release key to stopdecrement of value.
-
Press “ENTER” key to save the setting value.
P V
:
3 0 .
2 °
C
F 2
3 0 .
0 °
C
Fig. 15
Default Setting:
Set t ing Parameters Defaul t Value
Z-BAND
1.5°C
DIFF
0.5°C
P-BAND
2.0°C
OFFSET
0°C
MODE
COOL
REVERSE
OFF
DISPLAY
OFF
MANUAL
OFF
SP
21°C
F1 ( I )
15 SEC
ALARM (F2)
30°C
OUTPUT
2 to 10Vdc
IMPORTANT: Before setting, please check the followingpoints.
1.
Inspect the controller visually& check the pushbuttonbefore connecting themainpower.
2.
There should not be any abnormal phenomena or obvious shipping damage.
3.
Check the Selector Switch&make sure that the switch is set at the right position.