Wellworth Ecatalog - page 33

V5050A FLANGED LINEARVALVEPN16
APEN0H-002TW01A0604
2
SIZESANDFLOWCAPACITIES
Order Number
ValveSize
k
VS
V5050A2088
DN100
140
V5050A2106
DN125
220
V5050A2114
DN150
310
INSTALLATION
Water shouldmeet VDI 2035 requirements.
Do not install valvewith stem below the horizontal.
Fluid flowmust correspondwith the arrowdirection on the
valve body.
The installation of a strainer is strongly recommended.
REPAIRPACKINGKIT
Part No.: R 43 176 754 - 005
ACTUATORS
Electric actuators
Actuator (1800N)
ValveSize
M6421B
M7421B
DN100 - DN150
Pneumatic actuators
Actuator
Valve
Size
Direct
Acting
Positioner
Model
Size
MP953A
13"
DN100 -
x
yes
MP953C
13"
DN150
x
no
CLOSEOFFPRESSURERATINGS in kPa
Electric actuators
Actuator
ValveSize
Model
Force
DN100
(k
VS
140)
DN125
(k
VS
220)
DN150
(k
VS
310)
ML6421B, ML7421B
1800N
150
120
80
Pneumatic actuators
ActuatorModel
Actuator Spring
Range
Air Pressure in
Actuator
ClosedValve
Seat
ValveSize
DN100
DN125
DN150
MP953C; (13“)
14-48 kPa
(2-7PSI)
0 kPa
upper
110
150
70
150
45
150
MP953A,C; (13“)
14-48 kPa
(2-7PSI)
115 kPa
lower
150
150
150
150
100
120