Wellworth Ecatalog - page 42

ML7420A/ML7425A,B
3
EN0B-0624GE02R0399
Action
The direction of action can be changed by repositioning of
selector plugW3*. It is set by the factory such that the stem
extends at increasing signal and retracts at decreasing
signal.
CAUTION NO E
*Jumper plugsW1,W2 andW3 are accessible after the
cover hasbeen removed. They are locatedon the rear
sideof theprotection sheet of theprinted circuit board
(seeEN1C-0073 andEN1C-0074).
Output Signal ”POSITION”
An analog output signal 2 to 10Vdc ”POSITION” is available
which represents the actual actuator position. It can be used
for remote indication.
When the actuator stem is extended the output signal is
10Vdc.
Accessories
Auxiliaryswitches
The actuators can be equipped on sitewith an auxiliary
switch unit with two switches. Their switching points are
adjustable over the full length of the actuator stroke. The
switches can be used to switch pumps or provide remote
indication of any stroke position.
A cable glandPG13.5 is deliveredwith the unit.
Part number:
43191680-005
Auxiliarypotentiometer
Auxiliary potentiometers are available formounting on site.
They can be used as feedback potentiometer and or to
provide remote indication to the valve position.
A cable glandPG13.5 is deliveredwith the unit.
Part number:
43191679-011 (10k
)
Part number:
43191679-012 (220
)
HighTemperatureKit
(for applications >150
°
Cmedium temperature)
HighTemperatureKit,
Order Number
Valve
DN
43196000-001
V5011A/V5011K
V5013A/V5013G
V5011R/V5013R
V5328A/V5329A
15 - 40
15 - 40
15 - 50
15 - 32
43196000-002
V5011A
V5013A/V5013G
V5328A/V5329A
V5049A
V5050A
50
50
40 - 80
15 - 65
15 - 80
CLOSE-OFFPRESSURERATINGS in kPa
StemForce
600N
Stroke
20mm
Valve mm 15
20
25
32
40
50
65
80
Size inch
1/2
3/4
1
1 1/4
1 1/2
2
2 1/2
3
Valves
Close-Off PressureRatings
V5011R
1600
1600
1000
700
460
260
V5011K
1600
1600
1300
1000
V5013R
1600
1600
1000
700
460
260
V5328A
1600/1000 1000
1000
600
350
200
120
50
V5329A (PN16)
1000
1000
1000
790
480
260
160
100
V5329C (PN6)
600
600
600
600
480
260
160
100
V5049A
1600/1000 1000
1000
600
350
200
120
V5050A
1000
1000
1000
600
350
200
120
50
V5095A
1600
1600
1600
1600
1600
1600
1600
For specific data of above valves seeSpecificationDataNo.:
V5011R
EN0B-064
V5011K
EN0C-0560
V5013R
EN0B-065
V5328A
EN0C-0432
V5329A,C
EN0C-0434
V5049A
EN0C-0433
V5050A
EN0C-0435
V5095A
EN0C-0490
1...,32,33,34,35,36,37,38,39,40,41 43,44,45,46,47,48,49,50,51,52,...208