Wellworth Ecatalog - page 122

D15PPressure reducing valvewithbalanced seat
50
EN0H-1007GE23R0610 • Subject to change
Methodof Operation
Spring loadedpressure reducing valves operate bymeans of a
force equalising system. The force of a diaphragmoperates
against the force of an adjustment spring. If the outlet pressure
and therefore diaphragm force fall becausewater is drawn, the
then greater force of the spring causes the valve to open. The
outlet pressure then increases until the forces between the
diaphragm and the spring are equal again.
The inlet pressurehasno influence ineither openingor closingof
the valve. Because of this, inlet pressure fluctuation does not
influence theoutlet pressure, thusproviding inlet pressurebalan-
cing.
Options
D15P-... A= WithPN16 flanged connections to ISO 7005-2,
EN1092-2 cast iron housing
Special Versions available on request
Connection size
Connection size
DN 50
65
80
100
125
150
200
Weight
approx. kg 16.2
28.2
41.5
67
103
150
408
Dimensions
mm
L 230
290
310
350
400
480
600
H 282
315
356
418
487
573
1200
h 106
126
154
183
210
248
305
F 165
185
200
220
250
285
340
k
vs
-value
28
47
70
110
180
250
380
16
15
bar
0
5
Accessories
RV283P Check valve
Grey cast iron housing, powder coated inside and
outside. DIN/DVGW tested in compulsory test sizes
DN 65, DN80 andDN 100
FY69P Strainer
With doublemesh, grey cast iron housing, powder
coated inside and outside.
A=Mesh size approximately 0.5mm
F76S-F Reverse-rinsing filter
Redbronze housing and filter bowl. Available in sizes
DN 65 toDN 100, with filtermesh sizes 100 μm
or 200 μm
RV283P
FY69P
F76S-F
1...,112,113,114,115,116,117,118,119,120,121 123,124,125,126,127,128,129,130,131,132,...208
Powered by FlippingBook