D06FPressure reducingvalve
16
Subject tochange EN0H-1002GE23R0900
FN 09S
bar
6
8
10
4
2
0
M 07
RV 277
ZR 06K
VST 06A
VST06B
MethodofOperation
Spring loadedpressure reducing valvesoperatebymeansof a
force equalising system. The force of a diaphragm operates
against the force of an adjustment spring. If the outlet pressure
and therefore diaphragm force fall becausewater is drawn, the
then greater force of the spring causes the valve to open. The
outlet pressure then increases until the forces between the
diaphragm and the spring are equal again.
The inlet pressure has no influence in either opening or closing
of the valve. Because of this, inlet pressure fluctuation does not
influence the outlet pressure, thus providing inlet pressure
balancing.
Versions
D06F- . . . A =With threadedmaleconnections, clear filter
bowl – up to 40 °C
D06 F- . . . B = With threadedmale connections, brass filter
bowl – up to70 °C
D06 F- . . . E =Without fittings, with clear filter bowl
– up to 40 °C
Special versions available on request
Connectionsize
Accessories
FN 09S HABEDO
®
Retrofit filter
Reverse-rinsing filter for retro-conversion to a
filter combinationunit of D06Fpressure
reducing valvesmadeafter 1977.
M 07 Pressuregauge
Housingdiameter 63mm, rear connection threadG
1
/
4
".
Ranges: 0 – 4, 0 –10, 0 – 16or 0 – 25bar
Please indicateupper valueof pressure range
whenordering
ZR 06K Double ringwrench
For removal of spring bonnet and filter bowl of
D 06 F valveswith connection sizesR
1
/
2
" – 2"
RV 277 Inlet non-return valve
For D 06 Fwith connection sizesR
3
/
4
" – 2"
VST 06 Connectionset
Two threaded or solder connections
A= Threaded connections
B=Solder connections
Connectionsize
R
1
/
2
"
3
/
4
"
1"
1
1
/
4
"
1
1
/
2
"
2"
Nominal size
DN 15
20
25
32
40
50
Weight
approx. (kg)
0.8
1.0
1.4
2.0
3.3
4.5
Dimensions
(mm)
L
140
160
180
200
225
255
I
80
90
100
105
130
140
H 89
89
111
111
173
173
h
58
58
64
64
126
126
D
54
54
61
61
82
82
k
vs
-value
2.4
3.1
5.8
5.9
12.6
12.0
Peak flow rate (m
3
/h)
according toDIN 1988Pt 5:
Household installations
1.8
2.9
4.7
7.2
8.3
13.0
Commercial installations
1.8
3.3
5.4
8.6
13.7
21.2
IfBt No.
P-IX 1582/l
P-IX 1582/l
P-IX 1582/l
P-IX 1582/l
—*
—*
DVGW-Register No.
0432
0433
0896
0435
0436
0437
*Compulsory testing in sizesR
1
/
2
" toR1
1
/
4
"