V5088AFLANGEDLINEARVALVEPN16OR
EN0B-0433GE02R0299
2
SIZESANDFLOWCAPACITIES
Order Number Application ValveSize
k
VS
V5088A1005
Water
V5088A2003
Steam
PN16 DN100 160
V5088A1013
Water
V5088A2011
Steam
PN16 DN125 250
V5088A1021
Water
V5088A2029
Steam
PN16 DN150 360
.
INSTALLATION
•
Water shouldmeet VDI 2035 requirements.
•
Do not install valvewith stem below the horizontal.
•
Fluid flowmust correspondwith the arrowdirection on the
valve body.
•
The installation of a strainer is strongly recommended.
REPAIRPACKINGKIT
Part No.
R43 176 755 - 004
(DN 15 to 65)
R43176755 - 005
(DN 80 to 150)
ACTUATORS
Electricactuators
Actuator (1800N)
ValveSize
ML6421B
ML7421B
DN100 - DN150
Pneumaticactuators
Model
ValveSize Direct
Acting
Positioner
MP953A DN100 -
V
yes
MP953C DN150
V
no
CLOSEOFFPRESSURERATINGS IN kPa
Electricactuators
Actuator
ValveSize
Model
Force
DN100
(k
VS
140)
DN125
(k
VS
220)
DN150
(k
VS
310)
ML6421B, ML7421B
1800N
1000
1000
1000
Pneumaticactuators
ValveSize
ActuatorModel
DN100
DN125
DN150
MP953A,C
1000
1000
1000