Wellworth Ecatalog - page 63

KOMBI-F-II, KOMBI-F
EN0H-050GE25R0700
10
Honeywell AG • All rights reserved
FlowdiagramKombi-F-II, DN 65
Pre-setting
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 8,0
k
v
-value
2,98 5,30 6,64 7,80 9,60 12,1 15,2 19,0 23,6 29,1 35,2 41,3 47,0 52,1 60,7
Pre-setting
9,0 10,0=open
k
v
-value
67,9 k
vs
= 74,4